Head-mounted Two-wire Signal Conditioners 26RS
26RS Head-mounted Two-wire Signal Conditioners 26-UNIT
RTD TRANSMITTER
(isolated)
Functions & Features
• Accepts direct input from an RTD and provides a standard 4 – 20 mA DC signal
• Linearization and burnout
• Wide operating temperature range suitable for harsh environments
Typical Applications
• Mounting in a sensor connection head minimizes noise effect and signal degradation
MODEL: 26RS–[1][2]
ORDERING INFORMATION
• Code number: 26RS-[1][2]
Specify a code from below for each [1] and [2].
(e.g. 26RS-4/K/BL)
• Temperature range (e.g. 0 – 100°C)
[1] INPUT RTD (2- or 3-wire)
1: JPt 100 (JIS ’89)
(Usable range: -100 to +500°C, -148 to +932°F, min.span: 50°C, 90°F)
3: Pt 100 (JIS ’89)
(Usable range: -100 to +650°C, -148 to +1202°F, min.span: 50°C, 90°F)
4: Pt 100 (JIS ’97, IEC)
(Usable range: -100 to +850°C, -148 to +1562°F, min.span: 50°C, 90°F)
5: Pt 50Ω (JIS ’81)
(Usable range: -100 to +500°C, -148 to +932°F, min.span: 100°C, 180°F)
6: Ni 508.4 Ω
(Usable range: -50 to +200°C, -58 to +392°F; min.span: 30°C, 54°F)
Note: Consult M-System for 2-wire RTD
[2] OPTIONS (multiple selections)
Response Time (0 – 90 %)
blank: Standard (≤ 0.5 sec.)
/K: Fast Response (Approx. 25 msec.)
Burnout
blank: Upscale burnout