2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER
B3HU-1/A 2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER
(HART communication, intrinsically safe)
Functions & Features
• Universal input: mV, V, T/C, RTD, resistance, potentiometer and DC voltage
• High accuracy
• HART communication
• Intrinsically safe approval
• Programming via hand-held communicator or via PC
• A wide variety of T/C and RTD types
• User’s temperature table can be used
• Self diagnostics
• Input-output isolated
MODEL: B3HU–[1]/A
ORDERING INFORMATION
• Code number: B3HU-[1]/A
Specify a code from below for [1].
(e.g. B3HU-0/A)
• Use Ordering Information Sheet (No. ESU-7502). Factory standard setting will be used if not otherwise specified.
• Specify the country in which the product is to be used with the Safety Approval code 2.
[1] SAFETY APPROVAL
0: None
1: FM intrinsically safe
2: CENELEC intrinsic safety (ATEX)
OPTIONS
CJC Sensor
/A: External Sensor (must be specified)
RELATED PRODUCTS
• USB interface Bell202 modem (model: COP-HU)
Usable in ‘non-hazardous’ area only.
• Hand-held communicator
(Consult HART Communication Foundation (HCF) web
site: www.hartcomm.org. )
• AMS (version 6.0 or higher)
• Simatic PDM (version 6.0 or higher)
• PC configurator software (model: B3HUCFG)
Downloadable at M-System’s web site.
GENERAL SPECIFICATIONS
Construction: Small-sized front terminal structure
Connection: Euro type connector terminal
(Applicable wire size: 0.2 - 2.5 mm2 (pin terminals: 0.2 - 1.5 mm2), stripped length 8 mm)
Housing material: Flame-resistant resin (gray)
Isolation: Input to output
Burnout (except DC voltage input): Upscale, downscale or no burnout selectable (standard: upscale);
Also detects wire breakdown and overrange input exceeding the electrical design limit for DC voltage input.
Cold junction compensation (T/C): CJC sensor (included) to be attached to the input terminals
User-configurable items:
· Input sensor type
· Number of wires (RTD & resistance)
· Input range
· Inverted output
· Burnout
· Damping time (via HART only, standard: 0)
· Sensor calibration (via HART only)
· Output calibration
· Special linearization data (via HART only)
· HART communication mode
HART COMMUNICATION
Protocol: HART communication protocol
HART address range: 0 – 15 (factory set to 0)
Transmission speed: 1200 bps
Digital current: Approx. 1 mAp-p when communicating
Character format: 1 Start Bit, 8 Data Bits, 1 Odd Parity Bit,
1 Stop Bit
Distance: 1.5 km (0.9 miles)
HART communication mode: Master-Slave Mode and Burst Mode (factory set to Master-Slave)
HART network mode: Point-to-Point Mode and Multi-drop Mode; automatically set to Multi-drop Mode when the address is set to other than 0.
INPUT SPECIFICATIONS
The input is factory set for use with K thermocouple, 0 to 100°C.
See Table 1 for the available input type, the minimum span and the maximum range.
■ DC mV & V
Input resistance: ≥ 1 MΩ
■ Thermocouple
Input resistance: ≥ 1 MΩ
Burnout sensing: 130 nA ±10 %
■ RTD (2-wire, 3-wire or 4-wire)
Excitation: 0.2 mA ± 10 %
Allowable leadwire resistance: Max. 20 Ω per wire
■ Resistance (2-wire, 3-wire or 4-wire)
Excitation: 0.2 mA ±10 %
Allowable leadwire resistance: Max. 20 Ω per wire
■ Potentiometer
Excitation: 0.2 mA ±10%
Allowable leadwire resistance: Max. 20 Ω per wire
OUTPUT SPECIFICATIONS
Output range: 4 – 20 mA DC
Operational range: 3.8 – 21.6 mA
Load resistance vs. supply voltage:
Load Resistance (Ω) = (Supply Voltage (V) – 12 (V))
÷ 0.024 (A) (including leadwire resistance)
INSTALLATION
Supply voltage
· 12 – 42 V DC (non-approved)
· 12 – 28 V DC (approved)
Operating temperature: -40 to +85°C (-40 to +185°F)
(See Safety Parameters for use in a hazardous
location.)
Operating humidity: 0 to 95 %RH (non-condensing)
Mounting: DIN rail
Weight: 80 g (2.8 oz)
PERFORMANCE
Accuracy: See Table 1 and ‘Explanations of Terms.’
Cold junction compensation error: ±0.5°C or ±0.9°F
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span at -5 to +55°C [23 to 131°F]
Start-up time: Approx. 8 sec.
Response time: ≤ 2 sec. (0 – 90 %) with damping time
set to 0 and when not communicating via HART.
Supply voltage effect: ±0.003 % × [Output Span] / 1 V
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute
(input to output to ground)
EXPLANATIONS OF TERMS
■ ACCURACY
This transmitter’s accuracy is theoretically defined as the addition of A/D and D/A conversion errors:
Accuracy = A/D Conversion Error + D/A Conversion Error
The A/D conversion error means that measured as HART signal which is A/D converted from the analog input signal.
The D/A conversion error of this transmitter is relatively very small so that it does not really affect the unit’s overall performance.
The “Accuracies” given in Table 1 therefore equals the A/D conversion error.
The temperature drift (coefficient) or the cold junction compensation error is not included in the “Accuracy.”
■ CALCULATION EXAMPLES OF OVERALL ACCURACY IN %
• DC Voltage
1) 0 – 200 mV
Absolute value accuracy (Table 1): 40 μV
40 μV ÷ 20