MDC6 DC POWER SUPPLY
MDC6 DC POWER SUPPLY
(maintenance forecast monitor function, capacity 120 W)
Functions & Features
• Accepts 100 – 240 V AC and provides regulated 24 V DC output
• Maintenance forecast monitor function
MODEL:MDC6–12024A–M2
ORDERING INFORMATION
• Code number: MDC6-12024A-M2
CAPACITY
120: 120 W
OUTPUT VOLTAGE
24: 24 V DC
MONITOR
A: Maintenance forecast monitor function
POWER INPUT
AC Power
M2: 100 – 240 V AC
GENERAL SPECIFICATIONS
Construction: Front terminal access; terminal cover provided
Connection
Power input, output voltage: M4 screw terminals (torque 1.08 N·m)
Alarm output: Applicable wire size: 0.081 to 0.823 mm2, stripped length: 9 to 10 mm
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (beige); aluminum
SUPPLY OUTPUT
Output voltage: 24 V DC -10/+15 %; adjustable on the front (ripple 2.0 %p-p max.)
Load current: ≤ 5 A
Overload protection: Voltage drop characteristics (105 %)
Overload detecting: 105 % of the rated current
■ Alarm Output
Transistor: NPN (sink) type; 30 V DC max., 50 mA DC max.
Residual voltage at ON: ≤ 2 V
Leakage current at OFF: ≤ 0.1 mA
INSTALLATION
Power input
AC: Operational voltage range 85 – 264 V AC 50/60 Hz
Operating temperature: 0 to 50°C (32 to 122°F)
Operating humidity: 25 to 85 % RH (non-condensing)
Mounting: DIN rail
Weight: 550 g (1.21 lb)
PERFORMANCE
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)
Load effect: ≤ 1.5 %
Line voltage effect: ±0.5 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 3000 V AC @ 1 minute
(output voltage or alarm output to power input)
2000 V AC @ 1 minute (power input to ground)
1000 V AC @ 1 minute (output voltage or alarm output to ground)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EN 61204-3 (Class A)
Low Voltage Directive
EN 62477-1
RoHS Directive
Approval:
UL 508 (Class 2: per UL 1310)
CAN/CSA C22.2 No.14
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
CONNECTION DIAGRAM
MG CO., LTD.