IT60A1 DISCRETE INPUT TOWER LIGHT
IT60A1 Tower Light Series
DISCRETE INPUT TOWER LIGHT
(60 mm dia., 4 layers)
Functions & Features
• Lighting, blinking and buzzing are controllable with PLC.
• Bi-color lighting available in fourth layer
• Separable tension clamp terminal
• Switchable between positive and negative common for input
• Sensor excitation (24 V DC) incorporated
MODEL: IT60A1-4[1][2][3][4][5]D[6]-[7][8]
ORDERING INFORMATION
• Code number: IT60A1-4[1][2][3][4][5]D[6]-[7][8]
Specify a code from below for each [1] through [8].
(e.g. IT60A1-4RYGBWD1-M2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
LAMP LAYERS
4: 4 layers
[1] LAMP 1 COLOR
(1st layer from the top)
R: Red
Y: Amber
G: Green
B: Blue
W: White
[2] LAMP 2 COLOR
(2nd layer from the top)
R: Red
Y: Amber
G: Green
B: Blue
W: White
[3] LAMP 3 COLOR
(3rd layer from the top)
R: Red
Y: Amber
G: Green
B: Blue
W: White
[4] LAMP 4 COLOR
(4th layer from the top)
R: Red
Y: Amber
G: Green
B: Blue
W: White
[5] LAMP 5 COLOR
R: Red
Y: Amber
G: Green
B: Blue
W: White
N: None
MOUNTING
D: Direct mounting
[6] DESIGN TYPE
1: Type 1
2: Type 2 (with dummy antennae)
(refer to outline dimensions)
[7] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[8] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
GENERAL SPECIFICATIONS
Degree of protection: IP 65, vertical mounting only (bottom connectors excluded)
Connection
Power input/Input: Separable tension clamp terminal
Applicable wire size: 0.2 to 1.5 mm2, stripped length 10 mm
Recommended solderless terminal:
AI0,5-10WH 0.5mm2 (Phoenix Contact)
AI0,75-10GY 0.75mm2 (Phoenix Contact)
Housing material: Flame-resistant resin (white)
Lens: Flame-resistant resin (transparent)
Isolation: Discrete input to power input to FE1 (Functional Earth)
DIP SW Setting: Frequency of lamp blinking and buzzing discontinuance, buzzing volume level, input specification. (refer to the instruction manual)
Power LED: Green light turns on when the power is supplied.
Lamp: Red, amber, green, blue and white LEDs
on/blinking (approx. 2 Hz, 10 Hz)
Buzzing: Approx. 3.3 kHz
Interval: continuous/intermittent (approx. 2 Hz, 10 Hz)
INPUT SPECIFICATIONS
■ Discrete Input: Dry contact, open collector PNP NPN
Input resistance: Approx. 50 kΩ
Common: Negative common NPN, positive common PNP
Sensing: Approx. 24 V DC
ON/OFF level: ≤ 4 V / ≤ 10 kΩ for ON; ≥ 20 V / ≥ 100 kΩ for OFF
INSTALLATION
Power consumption
•AC: Approx. 5 VA at 100 V
Approx. 7 VA at 200 V
Approx. 8 VA at 240 V
•DC: Approx. 2.5 W; approx. 100 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas
Mounting: Direct mounting
Mounting direction: Vertical
Weight: 1.4 kg (3.1 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(Discrete input to power input to FE1)
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
DIMENSIONS unit: mm
MOUNTING REQUIREMENTS unit: mm
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
M-System Vietnam






