• 4 digit (±9999) panel meter
• Scaling and HOLD functions
• High visible, 0.8" (20.3mm) high and bright LED
MODEL: 40DV–[1]–[2][3]
ORDERING INFORMATION
• Code number: 40DV-[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 40DV-V1-K3/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
[1] INPUT
Current
A1: ±199.9 μA DC (Conformance range)
(Input range: Approx. -219 – +219 μA, Input resistance: 1 kΩ)
A2: ±1.999 mA DC (Conformance range)
(Input range: Approx. -2.19 – +2.19 mA, Input resistance: 100 Ω)
A3: ±19.99 mA DC (Conformance range)
(Input range: Approx. -21.9 – +21.9 mA, Input resistance: 10 Ω)
A4: ±199.9 mA DC (Conformance range)
(Input range: Approx. -219 – +219 mA, Input resistance: 1 Ω)
A5: ±1.999 A DC (Conformance range)
(Input range: Approx. -2.19 – +2.19 A, Input resistance: 0.1 Ω)
A: 4.00 – 20.00 mA DC (Conformance range)
(Input range: Approx. 2.4 – 21.6 mA, Input resistance: 10 Ω)
Voltage
V1: ±199.9 mV DC (Conformance range)
(Input range: Approx. -219 – +219 mV, Input resistance: ≥ 100 MΩ)
V2: ±1.999 V DC (Conformance range)
(Input range: Approx. -2.19 – +2.19 V, Input resistance: ≥ 100 MΩ)
V3: ±19.99 V DC (Conformance range)
(Input range: Approx. -21.9 – +21.9 V, Input resistance: 10 MΩ ±5 %)
V4: ±199.9 V DC (Conformance range)
(Input range: Approx. -219 – +219 V, Input resistance: 10 MΩ ±5 %)
V5: ±600 V DC (Conformance range)
(Input range: Approx. -659 – +659 V, Input resistance: 10 MΩ ±5 %)
(CE not available)
6: 1.00 – 5.00 V DC (Conformance range)
(Input range: Approx. 0.6 – 5.4 V, Input resistance: 10 MΩ ±5 %)
[2] POWER INPUT
AC Power
K3: 100 – 120V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz)
L3: 200 – 240V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±20 %, ripple 10 %p-p max.)
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
Moving parts and indicators are not coated.
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-9532)
GENERAL SPECIFICATIONS
Construction: Panel flush mounting
Connection: M3 screw terminals (torque 0.6 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to power
A/D conversion: Σ – Δ
Sampling rate: 10 times/sec. (100 msec.)
Averaging: None or moving average
Setting: (Front button)
• Scaled range
• Moving average
• Brightness
• Others
■Recommended solderless terminal
DISPLAY
Display: 4 digits of 20.3 mm (0.8 inch) height, 7-segment, red LED
Display range: -9999 to 9999
Scaling range for measurement range (conformance range): -9999 to 9999 counts
Decimal point position: 10-1, 10-2, 10-3 or none
Zero indication: Higher-digit zeros are suppressed.
Over-range indication: '-9999' or '9999' blinking for display values out of the display range. 'S.ERR' blinks surpassing the permissible range.
Engineering unit indication: Sticker label attached
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,
cm, mm, m, m/sec, mm/min, cm/min, m/min,
m/h, m/s2, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m3, m3/sec,
m3/min, m3/h, Nm3/h, N·m, N/m2, g, kg, kg/h,
N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,
kJ, MJ, rpm, sec, min, pH, %, ppm, etc.
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated
■ Hold Input: Dry contact input
Detecting level: ≤ 0.8 V
Sensing: Approx. 2.1V DC, 0.03 mA
INSTALLATION
Power consumption
•AC:
Approx. 1.6 VA for 100 – 120 V
Approx. 1.0 VA for 200 – 240 V
•DC: Approx. 0.5 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Panel flush mounting
Weight: 160 g (0.35 lb)
PERFORMANCE
Accuracy (for each input code)
A1: ±0.1 % rdg ±1 digit
A2: ±0.1 % rdg ±1 digit
A3: ±0.1 % rdg ±1 digit
A4: ±0.1 % rdg ±1 digit
A5: ±0.3 % rdg ±1 digit
A: ±0.1 % rdg ±1 digit
V1: ±0.1 % rdg ±1 digit
V2: ±0.1 % rdg ±1 digit
V3: ±0.1 % rdg ±1 digit
V4: ±0.1 % rdg ±1 digit
V5: ±0.15 % rdg ±1 digit
6: ±0.1 % rdg ±1 digit
("1 digit" is multiplied by scaling-multiple. Even in case the scaling-multiple is less than 1, multiply by 1.)
Temp. coefficient: ±(0.01 % rdg +0.3 digits)/℃
("0.3 digits" is multiplied by scaling-multiple. Even in case the scaling-multiple is less than 1, multiply by 1.)
Scaling-multiple = | (Display Scaling Value B - Display Scaling Value A) ÷ (default Display Scaling Value B - default Display Scaling Value A) |
Line voltage effect: ±1 digit over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute (input to power to ground)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category I (input)
Installation Category II (power)
Pollution degree 2
Input to power: Reinforced insulation (300 V)
RoHS Directive
DISPLAY HOLD COMMAND
Displayed value is held with an external HOLD command input. Connect the contacts across HOLD to COM.
■WIRING EXAMPLES
EXTERNAL VIEW
PARAMETER LIST
■ SCALING SETTING MODE
■ DISPLAY SETTING MODE