43DV2 DC INPUT DIGITAL PANEL METER

Liên hệ Còn hàng

Digital Panel Meters 43 Series

DC INPUT DIGITAL PANEL METER

(process meter)
Functions & Features
• -1999 to +9999 digital panel meter
• Scaling & Hold functions available
• Screwless spring terminal

MODEL: 43DV2–[1][2]–R[3]

ORDERING INFORMATION

• Code number: 43DV2–[1][2]–R[3]
Specify a code from below for each of [1] through [3].
 (e.g. 43DV2-SAD-R/Q)
• Specify the specification for option code /Q
 (e.g. /SET)

[1] INPUT

DC Voltmeter (Without scaled range)
V1: ±199.9 mV DC (Conformance range)
(Input range: -219 – +219 mV, Input resistance: ≥1 MΩ)
V2: ±1.999 V DC (Conformance range)
(Input range: -2.19 – +2.19 V, Input resistance: ≥1 MΩ)
V3: ±19.99 V DC (Conformance range)
(Input range: -21.9 – +21.9 V, Input resistance: ≥1 MΩ)
Process Meter
S4: 0 – 10 V DC (Conformance range)
(Input range: -1 – +11 V, Input resistance: ≥1 MΩ)
S5: 0 – 5 V DC (Conformance range)
(Input range: -0.5 – +5.5 V, Input resistance: ≥1 MΩ)
S6: 1 – 5 V DC (Conformance range)
(Input range: 0.6 – 5.4 V, Input resistance: ≥1 MΩ)
S0: Specify voltage (See INPUT SPECIFICATIONS)
SA: 4 – 20 mA DC (Conformance range)
(Input range: 2.4 – 21.6 mA, Input resistance: 20 Ω)
SB: 0 – 20 mA DC (Conformance range)
(Input range: -2 – +22 mA, Input resistance: 20 Ω)
SC: 0 – 10 mA DC (Conformance range)
(Input range: -1 – +11 mA, Input resistance: 40.2 Ω)
SG: 0 – 1 mA DC (Conformance range)
(Input range: -0.1 – +1.1 mA, Input resistance: 402 Ω)
SJ: 0 – 5 mA DC (Conformance range)
(Input range: -0.5 – +5.5 mA, Input resistance: 80.6 Ω)
SZ: Specify current (See INPUT SPECIFICATIONS)

[2] TERMINAL BLOCK

S: Screwless spring terminal
D: Separable screwless spring terminal

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[3] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-9422)

GENERAL SPECIFICATIONS

Construction: Panel flush mounting
Connection
Terminal block "S": Screwless spring terminal
Applicable wire size 1.0 to 1.3 mm2, stripped length 8 mm
Terminal block "D": Separable screwless spring terminal
Applicable wire size 1.0 to 1.3 mm2, stripped length 8 mm
Housing material: Flame-resistant resin (gray)
Isolation: Input to power
A/D conversion: Σ – Δ
Sampling rate: 5 times/sec. (200 msec.)
Averaging: None or moving average
Setting: (Front button)
• Scaled range (Process meter)
• Calibration (DC Voltmeter)
• Moving average
• Brightness
• Others

DISPLAY

Display: 4 digits of 10.2 mm (.4”) height, 7-segment, red LED
Display range: -1999 to 9999
Zero indication: Higher-digit zeros are suppressed.
■DC Voltmeter
Over-range indication: 'S.ERR' blinks when out of the input range.
■Process meter
Scaling range for measurement range (conformance range): -1999 to 9999 counts
Decimal point position: 10-1, 10-2, 10-3 or none
Over-range indication: '-1999' or '9999' blinking for display values out of the display range.
 'S.ERR' blinks surpassing the permissible range.
Engineering unit indication: Sticker label attached
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,
cm, mm, m, m/sec, mm/min, cm/min, m/min,
m/h, m/s2, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m3, m3/sec,
m3/min, m3/h, Nm3/h, N·m, N/m2, g, kg, kg/h,
N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,
kJ, MJ, rpm, sec, min, pH, %, ppm, etc.

INPUT SPECIFICATIONS

■ DC Current: Input resistor incorporated
Input resistance: 5 - 250 [Ω]*
Conformance range: 0 – 50 mA DC
Minimum span: 1 mA
Operational range: -10  - +110 % of input span
* Calculated as follows;
Input resistance [Ω] = 250 ÷ Input current at 100 % [mA]
■ DC Voltage
Input resistance: ≥ 1 MΩ
Input range: 0 – 19.99 V DC
Minimum span: 0.1 V
Operational range: -10 - +110 % of input span
■ Hold Input: Dry contact input
Detecting level: ≤ 0.8 V
Sensing: Approx. 2.1V DC, 0.03 mA

INSTALLATION

Power consumption: Approx. 0.15 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Panel flush mounting
Weight: 40 g (1.4 oz)

PERFORMANCE

Accuracy
• DC Voltmeter: ±0.1 % rdg ±1 digit
• Process meter:  ±0.1 % rdg ±1 digit × scaling-multiple
(When the scaling-multiple is less than 1, rounded up to 1.)
Temp. coefficient
• DC Voltmeter: ±(0.01 % rdg + 0.3 digits)/℃
• Process meter:
±(0.01 % rdg + 0.3 digits × scaling-multiple)/℃
(When the scaling-multiple is less than 1, rounded up to 1.)
Scaling-multiple = | (Display Scaling Value B - Display Scaling Value A) ÷ (default Display Scaling Value B - default Display Scaling Value A) |
Line voltage effect: ±1 digit over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @1 minute (input to power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

DISPLAY HOLD COMMAND

Displayed value is held with an external HOLD command input.  Connect the contacts across HOLD to COM.
■WIRING EXAMPLES

EXTERNAL VIEW

PARAMETER LIST

■ SCALING SETTING MODE (Process meter, applicable to input code Sx only)

■ CALIBRATION MODE (Only for DC Voltmeter, applicable to input code V1, V2, V3)

■ DISPLAY SETTING MODE

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm

MOUNTING

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG CO., LTD.
www.mgco.jp
Tags: