Ascon - Bộ Điều Khiển Lập Trình K49
Hãng Sản Xuất: Ascon
Xuất Xứ: Italy
Tình Trạng: Còn Hàng
Bộ Điều Khiển Lập Trình K49

Dual Display mini-programmer controller
- Panel mount controller 48x48 mm
- 1 Configurable probe input
- Up to 3 outputs
- PID controller with:
* Independent timer (optional)
* 8 segment programmer (optional)
* Wattmeter
* Counter for worked days and hours
* Compressor protection timer - TTL port
- 2 display lines, 4 digit, h 7 mm, red and green colour
Process inputs:
1 temperature probe input
- Thermocouples: J, K, R, S,T
- PTC KTY81-121 (990 Ω @ 25 °C)
- NTC 103AT-2 (10KΩ @ 25 °C)
- RTD: Pt100
- Voltage (V): 0..1 V, 0/1...5 V , 0/2...10 V
- Voltage (mV): 0...50 mV, 0...60 mV, 12 ...60 mV
- Current (mA): 0/4...20 mA
- Custom linearisation and IR probes (J.K type)
Overall accuracy: ± (0,5 % span ± 1 digit @25 °C); Tc S: ± (1 % span ± 1 digit @ 25 °C)
Keyboard
Mechanical: 4 multifunction keys
Process outputs
Up to 3 outputs:
OUT1
- RELAY SPST-NO, 8A
- SSR Drive
OUT2
- RELAY SPST-NO, 8A
- SSR Drive
OUT3
- RELAY SPST-NO, 5A
- SSR Drive
Power supply:
- 24 VAC/VDC
- 100… 240 VAC (50/60 Hz)
Transmitter power supply: 10 VDC (±10%), 20 mA max.
Functions
- ON/OFF control with neutral zone
- PID single action or double action (Heat/Cool) with overshoot control
- Bumpless ramp to set point change
- Start-up delay
- Independent timer with 5 functioning modes (optional)
- Digital Setpoint retransmission (Note 1)
- Up to 4 memorized setpoints
- 8 segment programmer with events recovery, 2 events and guaranteed soak (optional)
- Wattmeter for calculating the instantaneous power and energy used
- Counter for days and hours worked
with programmable threshold for programmed maintenance
- Timer
Autotuning
- Adaptive Autotuning
- Oscillatory
- Fast
Alarms
- Up to 3 configurable alarms + loop break alarm
Communication and programming:
Interfaces
Communication on TTL port to:
- Universal programming key
- Remote display
Programming/configuration tools:
- Configurable parameter level “Promotion”
- Configuration software available for PC
Installation
Mounting method: panel mount
Case dimensions: 48 x 48 mm (1/16 DIN)
Connections
Communication port connection
5 Pole TTL Port
Connection
12 poles 2.5 mm² screw terminals block
Front protection: IP 65 (with gasket) according to EN 60070-1 for indoor use
Display and indicators
2 display lines, 4 digit, h 7 mm, red and green colour
Connectable to:
- Programming key A01 for PC connection, backup and other functions
- SCADA for monitoring, traceability and remote management
- DX and DY gateways for remote monitoring