MAAC LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE
MAAC
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR
FOR POWER SUPPLY USE
(5A; high discharge current capacity; life monitor/surge counter)
Functions & Features
•Designed specifically for AC power supplies up to 5 amps
•Discharge current capacity 10000 A
•Life monitor function helps you to decide when you should replace the M-RESTER; reduces maintenance and prevents downtime
•LED display and alarm contact output indicate
the degradation and life span of the surge protection circuits
•No power supply interruption even when the unit is degraded or at the end of its life
MODEL: MAAC–[1]
ORDERING INFORMATION
• Code number: MAAC–[1]
Specify a code from below for [1].
(e.g. MAAC-100)
[1] OPERATIONAL VOLTAGE
100: 100 V / 110 V / 120 V AC
200: 200 V / 220 V / 240 V AC
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel
Housing material: Flame-resistant resin (black)
Indicators
Surge counter: 7-segment, 3-digit, red LED; The LED flashes when the life span of the discharge element is near to the end, recommending replacement of the M-RESTER; turns off when the life is ended.
PWR: The green LED turns on while the circuit is alive and the internal fuse is not blown; and is off when the power supply is removed or the fuse is blown.
ALARM: The LED turns on when the life span of the discharge element has ended and/or the voltage limiter has been degraded.
Degradation judged: When the leakage current at the voltage limiter exceed approx. 3mA; or when the fuse is blown.
Life time judged: When the number of discharges of the discharge element reaches the expected life span.
Alarm output: The N.C. contact is on when the life span of the discharge elements has ended, when the voltage limiter has degraded, and/or when the power supply is removed.
Rating: 125 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 250 V AC or 110 V DC
Maximum switching power: 62.5 VA or 30 W
Minimum load: 5 V DC @ 1 mA
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 500 g (1.1 lb)
PERFORMANCE
Operational voltage range:
90 – 132 V AC (MAAC-100)
180 – 264 V AC (MAAC-200)
50/60 Hz
Approx. 2 VA at 100 V AC
Approx. 2 VA at 200 V AC
Approx. 4 VA at 264 V AC
Discharge voltage (peak valtage)
Line to line:
190 V min. (MAAC-100)
410 V min. (MAAC-200)
Line to ground: 400 V min.
Maximum surge voltage
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Line to line: 400 V max. (MAAC-100)
750 V max. (MAAC-200)
Line to ground: 900 V max.
Withstand voltage of protected equipment between the circuit and the metal housing must be 1000V AC or more.
Response time: ≤ 0.01 μsec.
Leakage current
Line to line: ≤ 26 mA at 100 V AC (MAAC-100)
≤ 13 mA at 200 V AC (MAAC-200)
Line to ground: ≤ 0.1 mA at 300 V AC
Discharge current capacity: 10000 A (8/ 20 μsec.)
Maximum load current: 5 A
Internal series resistance: ≤ 0.5 Ω including return
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (alarm output)
Installation Category II (power)
Pollution degree 2
Alarm output to power: Reinforced insulation (300 V)
RoHS Directive
EXTERNAL VIEW
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
--------------------
CÔNG TY CỔ PHẦN KỸ THUẬT VÀ THƯƠNG MẠI THIẾT BỊ CÔNG NGHIỆP NTD
Adress: No. 28, Alley 36 Co Linh Street, Group 7, Long Bien Ward, Long Bien District, Hanoi City, Vietnam.
Hotline: 0971961212
Mail: sales@ntd-automation.com