MAL ONE-PORT SURGE PROTECTOR FOR POWER SUPPLY USE
MAL
Lightning Surge Protectors for
Electronics Equipment M-RESTER
ONE-PORT SURGE PROTECTOR FOR
POWER SUPPLY USE
(class I)
Functions & Features
• Designed to protect electronics equipment from direct lightning surges entering through power supply cables.
• Connected in parallel between the power and ground lines regardless of load current
• High discharge current capacity of 25 kA (10/350 μsec.)
• Detect degraded discharge element, with a relay contact output to alert the failure status.
Typical Applications
• Installation in service entrance switch gear
MODEL: MAL–[1][2]
ORDERING INFORMATION
• Code number: MAL-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. MAL-230Y)
[1] OPERATIONAL VOLTAGE
230: 230 V AC
400: 400 V AC
[2] ALARM OUTPUT
A: With
Y: Without
(Select '230' for 'Operational Voltage' code.)
RELATED PRODUCTS
• Wiring bridge (model: CNB2)
• One-port surge protector between N and PE (model: MALN)
■ Coordination of surge protector (Class II)
Unnecessary when this surge protector and the device to protect are adjacent (less than 10 m).
• One-port surge protector for power supply use (model: MAKF)
• One-port surge protector between N and PE (model: MAKN)
• Lightning surge protector for three-phase power supply (model: MAT2)
GENERAL SPECIFICATIONS
Degree of protection: IP20
Surge protection type: Voltage switching type one-port SPD (IEC 61643-1)
Discharge element: Gas discharge tube
Connection
Line: Push-lock screw terminal (torque: 4.5 N·m)
Alarm output: Euro type connector terminal
(torque: 0.25 N·m)
Applicable wire size
Line connection: 8 - 35 mm2, stripped length 15 mm
Alarm output: 0.2 - 1.5 mm2, stripped length 7 mm
Housing material: Flame-resistant resin
Alarm output: Trips when the thermal breaker operates. (N.C. contact)
Rated load: 250 V AC @ 0.5 A
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN rail
Weight: 230 g (0.51 lb)
PERFORMANCE
Response time: ≤ 50 nsec.
Follow current interrupting rating
• MAL-230x: 4 kA
• MAL-400A: 0.75 kA
Maximum discharge current: 25 kA (10/350 μsec.)
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to alarm output)
Dielectric strength: 2000 V AC @ 1 minute (line to alarm output)
Surge protection: IEC 61643-1 Class I
STANDARDS & APPROVALS
EU conformity:
Low Voltage Directive
EN 61643-11
RoHS Directive
CONNECTION EXAMPLES
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY
--------------------
CÔNG TY CỔ PHẦN KỸ THUẬT VÀ THƯƠNG MẠI THIẾT BỊ CÔNG NGHIỆP NTD
Adress: No. 28, Alley 36 Co Linh Street, Group 7, Long Bien Ward, Long Bien District, Hanoi City, Vietnam.
Hotline: 0971961212
Mail: sales@ntd-automation.com