MDA-TL LIGHTNING SURGE PROTECTOR FOR ANALOG TELECOM LINE USE
MDA-TL
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR
ANALOG TELECOM LINE USE
(life monitor)
Functions & Features
• Designed specifically to protect telecommunication equipment from lightning surges entering through telecommunication line network
• Absorbing surges only without affecting instrumentation signal
• Life monitor function helps you to decide when you should replace the M-RESTER; reduces maintenance and prevents downtime
• LED display and alarm contact output indicate the degradation and life span of the surge protection circuits
MODEL: MDA–TL–[1]
ORDERING INFORMATION
• Code number: MDA-TL-[1]
Specify a code from below for [1].
(e.g. MDA-TL-M)
[1] POWER INPUT
AC Power
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
Telecom line: Modular jack or M3.5 screw terminals
(torque 0.8 N·m);
Line screw terminal connection must be handled by
qualified personnel.
Ground: M3.5 screw terminals (torque 0.8 N·m)
Modular jack cord: 6-pole, 2-core
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Alarm indicators
Power: The green LED turns on while the power is supplied.
Alarm: Tricolor LED (green/amber/red)
•Remains off when the power supply is first turned on.
•Green: The unit has received one or more surges.
•Amber: Replacement is recommended.
•Red: The life span has ended.
Life time judged: When the number of discharges
of the discharge element reaches the expected life span.
Alarm contact: The N.C. contact is on when the life span of the discharge elements has ended and/or when the power supply is removed.
Rating: 125 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 125 V AC or 110 V DC
Maximum switching power: 62.5 VA or 30 W
Minimum load: 5 V DC @ 1 mA
INSTALLATION
Power consumption
•AC: Approx. 2 VA at 100 V
Approx. 3 VA at 200 V
Approx. 4 VA at 240 V
•DC: Approx. 1.5 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting Frame BX-16H available
Weight: 150 g (0.33 lb)
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: ±190 V min.
Line to ground: ±180 V min.
Maximum surge voltage
Line to line: ±500 V max.
Line to ground: ±900 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time: ≤ 0.01 μsec.
Leakage current:
Line to line: ≤ 100 μA @ ±160 V DC
Line to ground: ≤ 100 μA @ ±160 V DC
Discharge current capacity
Modular jack connection: 500 A (8 / 20 μsec.)
Screw terminal connection: 10000 A (8 / 20 μsec.)
Maximum load current: 200 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
(surge protector circuit to alarm output to power)
Dielectric strength: 2000 V AC @ 1 minute (surge protector circuit to power to alarm output to ground)
Internal series resistance: Approx. 4 Ω including return
Maximum line voltage: ±160 V DC
Frequency band: Approx. 100 kHz/-3 dB at 600 Ω terminating resistance
EXTERNAL VIEW
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
CÔNG TY CỔ PHẦN KỸ THUẬT VÀ THƯƠNG MẠI THIẾT BỊ CÔNG NGHIỆP NTD
Adress: No. 28, Alley 36 Co Linh Street, Group 7, Long Bien Ward, Long Bien District, Hanoi City, Vietnam.
Hotline: 0971961212
Mail: sales@ntd-automation.com