MSP4D MINI-TOP ELECTRONIC ACTUATOR

Liên hệ Còn hàng

MSP4D

Final Control Elements

MINI-TOP ELECTRONIC ACTUATOR

(linear type; DeviceNet)
Functions & Features
• Small-size control valve actuator
• Direct connection to DeviceNet capable PLC
and other devices on the same network
• Easy wired
• Remote configuration via DeviceNet
• Uploading device information via DeviceNet for maintenance purpose
• 1/1000 high resolution
Typical Applications
• Small-diameter control valve used in food related plants or in co-generation systems
• Air-conditioning in buildings or plants
• Micro-flow control for pharmaceutical injection
 

MODEL: MSP4D-[1][2][3]-[4]R

ORDERING INFORMATION

• Code number: MSP4D-[1][2][3]-[4]R
Specify a code from below for each of [1] through [4].
  (e.g. MSP4D-271-CR)

[1] STROKE

1: 5 to 10 mm (.20” to .39”)
2: 8 to 15 mm (.31” to .59”)

[2] OPERATION TIME, THRUST

6: 24 sec. / 10 mm, 500 N
7: 30 sec. / 10 mm, 700 N

[3] OUTPUT STEM TYPE

6: M6 female thread, 0.75 pitch
8: M8 female thread, 1.0 pitch
1: M10 female thread, 1.25 pitch
D: M6 female thread, 1.0 pitch
E: M8 female thread, 1.25 pitch
F: M10 female thread, 1.5 pitch

[4] CE MARKING

C: With
0: Without

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Degree of protection: IP66 (IP67 connector)
Action: Direct or reverse (factory set to “reverse”)
(In “reverse” action, the output stem is retracted with an input signal increase.)
Operation at a communication error: Extend, retract or stop (DIP SW selectable; factory set to“stop”)
Node address: 0 – 63; DIP SW selectable
Baud rate: 125 k, 250 k, 500 k bps (DIP SW selectable; factory set to 125 kbps)
Circuit connection
  Communication
: 5-core microconnector, male
  Power: 4-core microconnector, male
Transmission cable: Approved for DeviceNet
(e.g. OMRON DCA1)
Power input cable: With connector
(e.g. OMRON XS2F or XS2WD42)
Housing material: Cast aluminum
Drive: Stepping motor
Insulation class: E
Position detection: Potentiometer
Isolation: Communication to power
Zero adjustment: 0 – 25 %
Span adjustment: 50 - 100 %
MS (Module Status) indicator: Bi-color (green/red)
LED indicates device status.
NS (Network Status) indicator: Bi-color (green/red)
LED indicates status of the communication link.
Manual operating handle: Not available

OUTPUT SPECIFICATIONS

■ Operation Time & Torque (at rated power voltage)
MSP4D-x6: 24 seconds / 10 mm, 500 N (112 lbf)
MSP4D-x7: 30 seconds / 10 mm, 700 N (157 lbf)

INSTALLATION

Current consumption
DC: Approx. 0.5 A
Supply voltage to network: 11 – 25 V DC supplied through the network terminal block
Supply current to network: 60 mA max.
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: 0.5 G (4.9 m/s2) max.
Mounting position: All directions 
Do not mount the actuator with its output stem or cable connector on the upside if the actuator is to be exposed to dripping water.
Weight: 1.5 kg (3.3 lb)

PERFORMANCE

Resolution: 1/1000 or 0.015 mm, whichever is greater, with 0.1 % deadband setting
Insulation resistance:
≥ 100 MΩ with 500 V DC (communication [except drain] to power or metallic housing)
≥ 100 MΩ with 100 V DC (power to metallic housing)
Dielectric strength:
1500 V AC @ 1 minute (communication [except drain] to power or metallic housing)
100 V AC @ 1 minute (power to metallic housing)

STANDARDS & APPROVALS

 EU conformity (CE marking)
EMC Directive  
    EMI EN 61000-6-4
    EMS EN 61000-6-2
RoHS Directive
    EN IEC 63000

COMMUNICATIONS

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY

--------------------

CÔNG TY CỔ PHẦN KỸ THUẬT VÀ THƯƠNG MẠI THIẾT BỊ CÔNG NGHIỆP NTD

Adress: No. 28, Alley 36 Co Linh Street, Group 7, Long Bien Ward, Long Bien District, Hanoi City, Vietnam.

Hotline: 0971961212

Mail: sales@ntd-automation.com

Tags: