R5-PS POWER SUPPLY MODULE

Liên hệ Còn hàng

ES-6110 Rev.15

R5-PS

Remote I/O R5 Series

POWER SUPPLY MODULE

MODEL: R5–PS[1][2]

ORDERING INFORMATION

• Code number: R5-PS[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R5-PSR/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] POWER INPUT

AC Power
K: 100 – 120 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 200 – 240 V AC
(Operational voltage range 170 – 264 V, 47 –  66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

NOTICE

■ RUN CONTACT OUTPUT
• Function of RUN contact output
  During a Network Module communicates normally with a master device (PLD or PC etc.), RUN contact output of Power Supply Module turns ON.
• When using with dual redundant communication or two system.
  During both Network Module or one of them communicates normally with a master device (PLD or PC etc.), RUN contact output of Power Supply Module turns ON.
• When using R5-PS with redundant or two system.
  RUN contact output works in same function for both cases.  However, when I/O capacity code of installation base is "05:5 slots (single communication mode)" or "09: 9 slots (single communication mode)", the RUN contact output of Power Supply Module installed in a Extender Power Module Base (model: R5-EX1) is not available.

GENERAL SPECIFICATIONS

Connection
Power input or RUN contact output: M3.5 screw terminals
  (torque 0.8 N·m)
Internal bus or internal power: Via the Installation Base (model: R5-BS)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Isolation: Internal bus or internal power to power supply to RUN contact output to FG
Power LED: Bi-color (red/amber) LED;
Red when the power is supplied; Amber at RUN contact output ON.
 RUN CONTACT OUTPUT
Contact turns ON (closed) while data from the host is normally received; OFF (open) with loss of communication for approx. 3 seconds.
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.

INSTALLATION

Power consumption
AC: Approx. 90 VA
DC: Approx. 45 W or 1.8 A
Output current: 1.5 A continuous at 21 V DC;
(Total current continuously consumed at the network modules and I/O modules must be within 1.5 A.)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS) or Extender Power Supply Module Base (R5-EX1)
Weight: 250 g (0.55 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (Internal bus or internal power to power input to RUN output to FG)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
 EN 61010-1, EN 61010-2-201
 Measurement Category II (RUN contact output)
 Installation Category II (power input)
 Pollution Degree 2
  Internal power or RUN contact output to power input to FG:
  Reinforced insulation (300 V)
  Internal power to RUN contact output: Basic insulation (300 V)
RoHS Directive

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG CO., LTD.
www.mgco.jp