R5-YS 4 - 20 mA OUTPUT MODULE

Liên hệ Còn hàng

ES-6120 Rev.11

R5-YS

Remote I/O R5 Series

4 - 20 mA OUTPUT MODULE

MODEL: R5-YS[1][2]/A[3]

ORDERING INFORMATION

• Code number: R5-YS[1][2]/A[3]
Specify a code from below for each of [1] through [3].
  (e.g. R5-YS1W/A/H/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] NO. OF CHANNELS

1: 1
2: 2

[2] COMMUNICATION MODE

S: Single
W: Dual

OUTPUT HOLD

/A: With output hold setting switch

[3] OPTIONS (multiple selections)

Load Resistance
blank: ≤ 300 Ω
/H: ≤ 600Ω (available only for 1-channel output type)
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Connection
  Internal bus: Via the Installation Base (model: R5-BS)
  Output: Euro type connector terminal
  (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 - 12),
   stripped length 7 mm)
  Internal power: Via the base (model: R5-BS)
Isolation: Output 1 to output 2 to internal bus or internal power
Output hold: Setting of output hold or off for communication error with side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

OUTPUT SPECIFICATIONS

Output range: 4 – 20 mA DC
Load resistance: 300 Ω max. (600 Ω max. with Option /H)

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 100 g (0.22 lb)

PERFORMANCE

Conversion accuracy: ±0.1 %
Data range: 0 – 10000 of the output range
Data allocation: 1 (2 for 2-channel type)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
With Option /H, ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output 1 to output 2 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

Output hold function:
In normal conditions, the module outputs the signal from the preferred internal bus A.
When an error is detected, the output is switched to the data from the internal bus B.
If both are in error, when the DIP switch on the side panel is OFF, the module holds and output the last received data. When the DIP switch 1 is ON, the module holds and output
-15 % of the selected range (approx. 1.6 mA).
Either internal bus A or bus B becomes normal, output recovers.

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM