R5T-YV DC VOLTAGE OUTPUT MODULE

Liên hệ Còn hàng

ES-6123 Rev.9

R5T-YV

Remote I/O R5 Series

DC VOLTAGE OUTPUT MODULE

(screw terminal block)

MODEL: R5T-YV[1][2][3]

ORDERING INFORMATION

• Code number: R5T-YV[1][2][3]
Specify a code from below for each of [1] through [3].
  (e.g. R5T-YV2W/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] NO. OF CHANNELS

1: 1
2: 2

[2] COMMUNICATION MODE

S: Single
W: Dual

[3] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Connection
  Internal bus: Via the Installation Base (model: R5-BS)
  Output: M3.5 screw terminal block (torque 0.8 N·m)
  Internal power: Via the base (model: R5-BS)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Isolation: Output 1 to output 2 to internal bus or internal power
Output range: Selectable with the side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

OUTPUT SPECIFICATIONS

 Narrow Span: -1 – +1 V, 0 – 1 V DC
Load resistance: 10 kΩ min.
 Wide Span: -10 – +10 V, -5 – +5 V, 0 – 10 V, 0 – 5 V, 1 – 5 V DC
Load resistance: 10 kΩ min.
 Output Range
Except -10 to +10 V DC
: -15 to +115 % of output range
-10 to +10 V DC: Approx. -11.5 to +11.5 V DC

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 110 g (0.24 lb)

PERFORMANCE

Output range v.s. conversion accuracy
(Narrow span) -1 – +1 V DC : ±0.1 (%)
  0 – 1 V DC : ±0.1
(Wide span) -10 – +10 V DC : ±0.05
  -5 – +5 V DC : ±0.05
  0 – 10 V DC : ±0.05
  0 – 5 V DC : ±0.05
  1 – 5 V DC : ±0.05
Data range: 0 – 10000 of the output range
Data allocation: 1 (2 for 2-channel type)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.2 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output 1 to output 2 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

Output hold function:
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
If both are in error, the module holds the signal and stands by until one of the communications recovers.
At the startup, it outputs -15 %  (or approx. -11.5 V) of the selected range until the communication is established and normal data is received.

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG CO., LTD.
www.mgco.jp
Tags: