PARAMETER GENERATOR M5XMST
M5XMST
Super-mini Terminal Block Signal Conditioners M5X-UNIT
PARAMETER GENERATOR
(PC programmable)
Functions & Features
• Provides a constant DC signal
• PC programmable
• High-density mounting
• Power LED
Typical Applications
• Various parameter settings for computers and
DCS’s
MODEL: M5XMST-1-R[1]
ORDERING INFORMATION
• Code number: M5XMST-1-R[1]
Specify a code from below for [1].
(e.g. M5XMST-1-R/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
EXTERNAL INTERFACE
◆ OUTPUT SIGNAL
1: DC output (field-selectable)
• Current output: 0 - 20 mA DC
• Voltage output: -5 - +5 V DC
• Voltage output: -10 - +10 V DC
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-2781)
RELATED PRODUCTS
• PC Configurator cable (model: COP-US)
• PC configurator software (model: M5CFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Construction: Terminal block
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Output to power
Output manual set point: -10.00 - +105.00 %
(Factory default setting: 0.00 %)
Output manual step: 0.01 - 5.00 %
(Factory default setting: 0.10 %)
UP/DOWN control: Double-throw, momentary SW (front)
Monitor output: 0 – 1 V for 0 – 100 % limit
Mis-operation preventer: Single-throw SW (front)
On the LOCK side, UP/DOWN control SW is disabled.
Stores current setting values to the non-volatile memory when sliding mis-operation preventer from UNLOCK to LOCK.
Power indicator LED: Green LED; Blinking patterns indicate different operating status of the transmitter.
Parameters: Stored in non-volatile memory; write/erase cycle endurance: less than 20 000
Programming: Downloaded from PC;
• output type
• output range
• zero and span
For detailed information, refer to the users manual for the PC configurator.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
OUTPUT SPECIFICATIONS
Standard default setting: DC current output 4 - 20 mA
Output type
• DC current output: 0 - 20 mA DC
• DC voltage output: -10 - +10 V DC
• DC voltage output: -5 - +5 V DC
(3 types can be switched by DIP switch and PC)
■ DC Current: 0 – 20 mA DC
Output range: 0 - 23 mA DC
Minimum span: 1 mA
Load resistance: 550 Ω
■ DC Voltage
• Output range -10 - +10 V DC
Voltage range: -11.5 – +11.5 V DC
Minimum span: 1 V
Load resistance: Output drive 1 mA max.
(ex. 0 - 10 V DC: 10 V ÷ 1 mA = 10 kΩ)
• Output range -5 - +5 V DC
Voltage range: -5.75 – +5.75 V DC
Minimum span: 500 mV
Load resistance: Output drive 1 mA max.
(ex. 1 - 5 V DC: 5 V ÷ 1 mA = 5000 Ω)
INSTALLATION
Power consumption: ≤ 1W
Operating temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 80 g (2.8 oz)
PERFORMANCE in percentage of span
Setting accuracy: ±0.1 %
Output accuracy (% of max. output range): ±0.02 %
(±0.04 % for current output)
Temp. coefficient: ±0.0075 %/°C (±0.004 %/°F) of max. span
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (output to power to ground)
ACCURACY AND CALCULATION EXAMPLES
■ Overall Accuracy
The accuracy includes output accuracy, which converts the setting accuracy and digital value into an analog signal.
The accuracy of the device is the total of the setting accuracy and the output accuracy.
Output accuracy
Output accuracy for the setting value span is shown as following formula.
Output accuracy = (output range ÷ output setting value span) × 0.02 %
For current output,
Output accuracy = (output range ÷ output setting value span) × 0.04 %
Calculation examples
Ex1: Output 4 - 20 mA
Output accuracy = (20 mA ÷ 16 mA) × 0.04 % = 0.05 %
Accuracy = setting accuracy 0.1 % + output accuracy 0.05 % = 0.15 %
Ex2: Output 0 - 10 V
Output accuracy = (20 V ÷ 10 V) × 0.02 % = 0.04 %