R1M-J3/MSR PC RECORDER (RTD or potentiometer input, 8 points)
R1M-J3/MSR
PC Recorders R1M Series
PC RECORDER
(RTD or potentiometer input, 8 points)
Functions & Features
• Industrial recorder on PC
• 8-point RTD or potentiometer inputs
• Easy system expansion via Modbus RTU
• Recorded data exportable to spreadsheet applications
MODEL: R1M-J3T-[1][2]
ORDERING INFORMATION
• Code number: R1M-J3T-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R1M-J3T-M2/MSR/Q)
• Specify the specification for option code /Q
(e.g. /C01)
FIELD TERMINAL TYPE
T: M3 screw terminals
[1] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS (multiple selections)
PC Recorder Software Package (must be specified)
/MSR: With
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
PACKAGE INCLUDES...
• PC Recorder Software CD
• 9-pin D-sub connector, straight type (1 m or 3.3 ft)
GNERAL SPECIFICATIONSE
Connection
Power input, transmission: Euro type connector terminal
(Applicable wire size: 0.2 – 2.5 mm2 (AWG24 – 12), stripped
length 7 mm)
RS-232-C: 9-pin D-sub connector (male)
(Lock screw No. 4-40 UNC)
Input: M3 screw terminals (torque: 0.6N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to RS-232-C or RS-485 to power
Node address setting: Rotary switch; 1 – F (15 nodes)
RUN indicator LED: Green light blinks in normal conditions.
COMMUNICATION
Baud rate: 38.4 kbps
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
■ RS-232-C
Standard: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
■ RS-485
Standard: Conforms to TIA/EIA-485-A
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.)
INPUT SPECIFICATIONS
Input: RTD or potentiometer input, 8 points
Maximum leadwire resistance: 20 Ω per wire (3-wire)
Sensing current: ≤ 1 mA
RTDs: JPt 100 (JIS ’89), Pt 100 (JIS ’89), Pt 100
(JIS ’97, IEC), Pt 50 Ω (JIS ’81), Ni 508.4 Ω, Pt 1000
Potentiometers: 0 – 100 Ω, 0 – 500 Ω, 0 – 1 kΩ, 0 – 10 kΩ
Sampling rate: 100 msec./8 points
• Trigger input: Dry contact; ON detected at ≤ 1.5 V
Sensing: Approx. 5 V DC @ 1 mA
INSTALLATION
Power consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lb)
PERFORMANCE (% of measuring range)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to RS-232-C or RS-485 to power to FG)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or RS-232-C/RS-485 to power: Reinforced insulation (300 V)
Input to RS-232-C/RS-485: Basic insulation (300 V)
RoHS Directive
PC RECORDER SOFTWARE
PC Recorder Software Package (model: MSRPAC-2010) is included with purchases of this model.
Refer to the MSRPAC-2010 data sheet for the contents of the package and the requirements for the PC to be prepared by the user.
EXTERNAL VIEW
MODBUS WIRING CONNECTION
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SYSTEM CONFIGURATION EXAMPLES
--------------------
CÔNG TY CỔ PHẦN KỸ THUẬT VÀ THƯƠNG MẠI THIẾT BỊ CÔNG NGHIỆP NTD
Adress: No. 28, Alley 36 Co Linh Street, Group 7, Long Bien Ward, Long Bien District, Hanoi City, Vietnam.
Hotline: 0971961212
Mail: sales@ntd-automation.com